For professional circuit-breaker analysis
The SA10 is the circuit breaker timer developed by professionals for
professionals. It has a built in micro Ohm meter/Ductor for measuring of static
and dynamic resistance of the breaker poles. It only weighs 11,6 kg/26 lbs.
The versatility
and precision that this unity offers is without question unchallenged, and it
will indeed be your best partner when testing circuit breakers.
Tests in areas with high induction at known problematic substations has proven
the SA10 to be the only circuit breaker timer that could withstand these extreme
conditions. It's rugged, it's small and highly appreciated by our customers.
Some
SA10 features:
- The well known powerful analysing software
BTS11
included.
- Built in a small metal carrying case.
- Fully compatible with our factory line test
equipment.
- No panel switches, just two push buttons Open and
Close.
- Supports both digital and analougue transducers.
- The only field test equipment with a built in
micro ohm measuring function.200A!
- Possibillity to use the “first trip” analysing
method.
- Weighs only 11,6 kg/26 lb.
- Automatic measurement of coil and motor
current/voltage.
- Designed for both offline and online analysis of circuit breakers.
|
 |
|
|
|
Contact Timing.
The contact input modules of SA10 supplies 120 VDC
at open contacts and 100 mA at closed. The
evaluation logic also distinguishes between a
possible preinsertion and the main contact in the
same operation. It is also possible to measure the
value of the preinsertion resistor with a reference
shunt. Timing for both the preinsertion and the main
contact is guarantied in any switchyard and at any
system voltage.
Number of main contact timing channels: 12(x2)
Number of auxiliary contact channels: 6
(The aux inputs can in environments with low
induction also be used as main contact inputs) |
 |
|
|
|
Coils and Motor.
Automatic measuring of circuit breaker coil and
motor current/voltage. Together with an adjustable
power unit it is very easy to perform minimum
function voltage test on the coils.
The SA10 uses 1 analogue channel to measure
coil voltage and current and 1 channel to
measure motor voltage and current.
For the coil 35 A AC/DC is possible for continuous
measurement, and for the motor 50A AC/DC. However if
necessary higher currents will pass for shorter
periods.
Read more
about testing the breaker coils>>
Read more
about testing the circuit breaker motor>> |
 |
|
|
|
Motion Measurements.
The SA10 supports both analogue and digital
transducers. A wide range of transducer fastenings
can also be supplied. Elcon International is the
official world wide supplier of transducer
fastenings for ABB-Breakers.
Number of digital transducer inputs: 3
Number of analogue transducer inputs: 3
Read
more about transducers and transducer fastenings>> |
 |
|
|
|
Static and dynamic resistance.
As the only field test equipment on the market with
a built in micro ohm meter it is a complete and
versatile unit. It generates 200 ADC and the value
is autmatically recorded into the system together
with your other measurents. In order to view the
breaker pole’s exact behavior during an operation
the dynamic resistance measurment function offers
great diagnostic possibillities.
Read more
about dynamic resistance measurements>> |
|
|
|
|
Analog inputs.
All in all the SA10 has 11 analog inputs,
however since our intension is to provide you with a
test equipment that is user friendly and circuit
breaker oriented they have been preset to handle
specific relevant functions such as coil and motor
voltages, currents, analog motion transducers etc.
It is of course possible to set most of the inputs
to handle other types of related input signals, such
as pressure sensors or temperature sensors or any
other type of analogue signal that may be relevant. |
 |
|
|
|
Communication.
Standars RS232 comunication is default. However, in
order to comply with safety regulations a bluetooth
comunication kit is available which allows the user
to take his laptop pc and move up to 100m(328ft)
away from the test-object.
Read about Wireless control>>
|
|
|
|
|
Switch sync breakers
Upon switching for example capacitor banks, shunt
reactors and power transformers it is common to use
a switch-sync relay for the cb. The SA10 allows for
full analysis of the point-on-wave switching
technology.
Read about Switch control and testing>>
|
|
|
|
|
First-trip
or online analysis.
In order to fully evaluate the condition of the
circuit breaker mechanism, the SA10 provides inputs
to test the breaker during an online operation. By
doing that you can capture the “First Trip” of a
breaker that has been stationary for a long time and
by that display how the breaker would perform in an
actual fault situation. Both trip and close
operations are possible online.
Read about first-trip analysis>> |
|
|
|