For professional circuit-breaker analysis
The SA5 has been developed for
professionals users that wish to fully analyze their medium Voltage circuit
breakers. Expand the contact timing tests to include travel results. It only weighs
8,6 kg/ 17lbs.
The versatility
and precision that this unity offers is without question unchallenged, and it
will indeed be your best partner when testing circuit breakers.
Tests in areas with high induction at known problematic substations has proven
the SA10 to be the only circuit breaker timer that could withstand these extreme
conditions. It's rugged, it's small and highly appreciated by our customers.
Some SA5 features:
- The well known powerful analysing software
BTS11
included.
- Built in a small metal carrying case. All cables
and accessories fits in the lid.
- Fully compatible with our factory line test
equipment.
- No panel switches, just two push buttons Open and
Close.
- Supports both digital and analougue transducers.
- Weighs only 8,6 kg/17 lb.
- Bulit in Printer option for operation without PC
- Automatic measurement of coil and motor
current/voltage.
|
 |
|
|
|
Contact Timing.
Three contact input modules of SA5 are
designated to be used as main contact channels, and
three are designated for auxiliary contact use. It
is possible however by using BTS11, to dedicate any
of the six channels to handle either.
Number of main contact timing channels: 3(6)
Number of auxiliary contact channels: 3
(The aux inputs can also be used as main
contact inputs) |
 |
|
|
|
Coils and Motor.
Automatic measuring of circuit breaker coil and
motor current/voltage. Together with an adjustable
power unit it is very easy to perform minimum
function voltage test on the coils.
The SA5 uses 1 analogue channel to measure
coil voltage and current and 1 channel to
measure motor voltage and current.
For the coil 35 A AC/DC is possible for continuous
measurement, and for the motor 50A AC/DC. However if
necessary higher currents will pass for shorter
periods. |
 |
|
|
|
Motion Measurements.
The SA5 supports both analogue and digital
transducers. A wide range of transducer fastenings
can also be supplied. Elcon International is the
official world wide supplier of transducer
fastenings for ABB-Breakers.
Number of digital transducer inputs: 1
Number of analogue transducer inputs: 1 |
 |
|
|
|
Analog inputs.
All in all the SA5 has 9 analogue inputs,
however since our intension is to provide you with a
test equipment that is user friendly and circuit
breaker oriented they have been preset to handle
specific relevant functions such as coil and motor
voltages, currents, analog motion transducers etc. |
 |
|
|
|
Communication.
Standard RS232 comunication is default. However, in
order to comply with safety regulations a bluetooth
comunication kit is available which allows the user
to take his laptop pc and move up to 100m(328ft)
away from the test-object. |
Read about Wireless control>> |
|
|
|
Printing
The use of a notebook PC and printers are
recomended. However as an option we supply the SA5
with a built in printer for basic results printouts. |
 |
|
|
|
Further functionality
The SA5 is intended to be used together with
medium Voltage breakers or if you only wish to
perform basic testing on High Voltage breakers.
Should you have increased testing requirements we
recommend our Field test equipment
SA10.
Additional features that you get with the SA10:
- Built in static and dynamic resistance measurement
capability.
- Two additional digital transducer inputs.
- Two additional analogue transducer inputs.
- 12 contact timing channels specially designed to
withstand high induction environments.
- 12 channels to measure pre-insertion resistors.
- 3 additional auxiliary contact channels.
- Possibility to perform Full analysis on breakers
with Switch synchronisation relays(switch control).
- Possibility to perform "First Trip" analysis. |
|
|
|