Static Resistance does not work?

Insert the fuse. Recharge your batteries.

SA10A not working on batteries?

The feature is removed.

Can't find Program Data on C: disk?

In BTS11 Menu Help Click Confiuguration Folder, or open Windows File Explorer and on the VIEW tab and tick hidden items.

Downloaded BTS11 but can't find any switch configurations?

Only UNB (Unknown Breaker) is included in BTS11.

No contact with DCR30 or POB35AD in BTS11?

Not selected Power supply under "Hardware" in BTS11

Does stroke turn different maneuvers into maneuvers?

Check that everything is tightened on the Sensor Attachment Kit - Flex bellows, lock nuts etc!

Main contacts flash strangely in the SA10A and the contact times in the graph get choppy?Uses SA10A on switches with high induction around!

Try parallel connecting over the main connectors on the SA10A straight down to the next connector. Red to Red-Black to Black!

Travel  graphs look weird or no travel graph at all?

Check out the Transducer/Cable function in the BTS11 Service menu! Sensor connected to the SA10's one of the sensor inputs T1-T2-T3. Go to menu Service/SA10/Transducer, have the sensor loose with cable connected! Restore so eg. T1 is at zero! Spin the sensor shaft pin a full revolution(360⁰) should be about 10,000 pulses. Turn back full turn, should be about 0, turn the other way, should be about -10,000 pulses, turn back again to about 0.If nothing abounds, both cable, sensor and contact output will work!

Where are the manuals?

Under Help menu in BTS11.

PROGRAM LOADER in Switch Analyser display.

Unit has lost it's program. The cause for this may be hardware fault. You can try updating firmware. See the user manual how to do this.

My equipment has broken/needs calibration! What to do?

On ELCON's Web page at the top left press "Return form" (RMA) or go on the link below!https://www.elcon.se/index.php/return-form-1Log in fill in and send and an RMA number will be created!The RMA number is then all linked to.

For other questions, please contact us at ELCON via email: This email address is being protected from spambots. You need JavaScript enabled to view it. or phone no:+46-(0)240-64 11 10